BESS Fire Protection Consulting

Project Name

xx Hotel BESS

Location

Pleasanton, CA

Market

Energy Storage / Hospitality

Service

BESS Fire Protection Consulting, NFPA 69 & NFPA 68 Analysis, Fire Alarm Permit Design & AMMR Support

Project xx Hotel BESS | Pleasanton, CA
Market Energy Storage / Hospitality
Services BESS Fire Protection Consulting, NFPA 69 Ventilation Analysis, NFPA 68 Deflagration Venting Analysis, Fire Alarm Permit Design, and Alternative Materials and Methods Request (AMMR) Support

An EPC client proposed a 20-ft 2,288 kWh containerized battery energy storage system (BESS) at xx Hotel in Pleasanton, California. During fire permit review, the local fire authority requested an engineering evaluation of how the proposed ventilation would limit the accumulation of flammable gases released during battery thermal runaway.

Engineering Fire Protection, LLC (EFP) prepared an NFPA 69 explosion prevention assessment. EFP reviewed UL 9540A fire test data and manufacturer HVAC performance data, then modeled how flammable gas concentrations would change over time inside the battery enclosure. The analysis evaluated whether continuous outdoor-air ventilation could keep gas concentrations below the design criterion and identified the operating and commissioning conditions needed to support the proposed approach.

EFP also performed an NFPA 68 deflagration venting analysis using FLACS computational fluid dynamics (CFD) modeling to evaluate pressure development and venting performance within the battery enclosure.

EFP prepared fire alarm permit drawings showing how the battery system would interface with the hotel’s existing fire alarm system for monitoring. The ventilation assessment and fire alarm drawings supported the project team’s AMMR and gave the local fire authority a technical basis for reviewing the proposed design.